Contact
N2XY XLPE Insulated Cable
These cables are used for electricity supply in low voltage installation system, They are suitable for:
· installation in indoors and outdoors
· in cable ducts
· under ground
· in power and switching stations
· local energy distributions
· industrial plants
where there is no risk of mechanical damage.
For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)
Details
Description: N2XY, XLPE Insulated Copper Power Cable
Conductors:Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.
Insulation:Cross-linked polyethylene XLPE
Insulation Colour:Natural or as required
Filler: Non-hygroscopic Material
Outer Sheath:Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath: Black
Voltage Rating (Uo/U):600/1000V Test Voltage: 3.5kV for 5 minutes
Physical Properties
Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90℃(XLPE insulation)
Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)
Short Circuit Temperature(5 seconds maximum duration): 140℃-160℃(PVC insulation);250℃(XLPE insulation)
Technical Data
0.6/1kV-3+1 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X2.5+1X1.5 | 0.7/0.7 | 1.8 | 12.3 | 200 | 7.41/12.1 | 28 | 39 |
3X4+1X2.5 | 0.7/0.7 | 1.8 | 13.4 | 260 | 4.61/7.41 | 37 | 51 |
3X6+1X4 | 0.7/0.7 | 1.8 | 14.6 | 350 | 3.08/4.61 | 47 | 64 |
3X10+1X6 | 0.7/0.7 | 1.8 | 16.9 | 480 | 1.83/3.08 | 65 | 86 |
3X16+1X10 | 0.7/0.7 | 1.8 | 19.4 | 760 | 1.15/1.83 | 84 | 110 |
3X25+1X16 | 0.9/0.7 | 1.8 | 22.8 | 1040 | 0.727/1.15 | 110 | 140 |
3X35+1X16 | 0.9/0.7 | 1.8 | 25.1 | 1420 | 0.524/1.15 | 135 | 170 |
3X50+1X25 | 1.0/0.9 | 1.8 | 28.2 | 1830 | 0.387/0.727 | 170 | 205 |
3X70+1X35 | 1.1/0.9 | 1.9 | 31.9 | 2500 | 0.268/0.524 | 215 | 250 |
3X95+1X50 | 1.1/1.0 | 2.1 | 35.7 | 3400 | 0.193/0.387 | 265 | 300 |
3X120+1X70 | 1.2/1.1 | 2.2 | 39.6 | 4300 | 0.153/0.268 | 310 | 345 |
3X150+1X70 | 1.4/1.1 | 2.3 | 43.6 | 5200 | 0.124/0.268 | 350 | 385 |
3X185+1X95 | 1.6/1.1 | 2.5 | 49.8 | 6500 | 0.0991/0.193 | 405 | 435 |
3X240+1X120 | 1.7/1.2 | 2.7 | 55.3 | 8500 | 0.0754/0.153 | 480 | 500 |
3X300+1X150 | 1.8/1.4 | 2.9 | 57.0 | 10000 | 0.0601/0.124 | 555 | 565 |
3X400+1X185 | 2.0/1.7 | 3.1 | 70.0 | 13300 | 0.0470/0.0991 | 640 | 640 |
0.6/1kV-4+1 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
4X2.5+1X1.5 | 0.7/0.7 | 1.8 | 13.2 | 220 | 7.41/12.1 | 28 | 39 |
4X4+1X2.5 | 0.7/0.7 | 1.8 | 14.5 | 320 | 4.61/7.41 | 37 | 51 |
4X6+1X4 | 0.7/0.7 | 1.8 | 15.9 | 420 | 3.08/4.61 | 47 | 64 |
4X10+1X6 | 0.7/0.7 | 1.8 | 18.5 | 650 | 1.83/3.08 | 65 | 86 |
4X16+1X10 | 0.7/0.7 | 1.8 | 21.3 | 950 | 1.15/1.83 | 84 | 110 |
4X25+1X16 | 0.9/0.7 | 1.8 | 25.7 | 1450 | 0.727/1.15 | 110 | 140 |
4X35+1X16 | 0.9/0.7 | 1.8 | 28.2 | 1850 | 0.524/1.15 | 135 | 170 |
4X50+1X25 | 1.0/0.9 | 1.9 | 28.9 | 2500 | 0.387/0.727 | 170 | 205 |
7X70+1X35 | 1.1/0.9 | 2.0 | 32.2 | 3450 | 0.268/0.524 | 215 | 250 |
4X95+1X50 | 1.1/1.0 | 2.2 | 36.9 | 4700 | 0.193/0.387 | 265 | 300 |
4X120+1X70 | 1.2/1.1 | 2.3 | 40.8 | 6000 | 0.153/0.268 | 310 | 345 |
4X150+1X70 | 1.4/1.1 | 2.5 | 44.7 | 7100 | 0.124/0.268 | 350 | 385 |
4X185+1X95 | 1.6/1.1 | 2.7 | 50.7 | 9000 | 0.0991/0.193 | 405 | 435 |
4X240+1X120 | 1.7/1.2 | 2.9 | 56.4 | 10400 | 0.0754/0.153 | 480 | 500 |
4X300+1X150 | 1.8/1.4 | 3.1 | 64.0 | 13500 | 0.0601/0.124 | 555 | 565 |
0.6/1kV-3+2 core copper conductor XLPE insulated PVC sheathed power cable | |||||||
No. of cores and nominal cross section | Thickness of Insulation | Thickness of Sheath | Approx. overall Diameter | Approx. weight | Max. DC resistance of conductor(20℃) | Current carrying capacity | |
(mm2) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | In Air(A) | In Ground(A) |
3X2.5+2X1.5 | 0.7/0.7 | 1.8 | 13.0 | 200 | 7.41/12.1 | 28 | 39 |
3X4+2X2.5 | 0.7/0.7 | 1.8 | 14.3 | 260 | 4.61/7.41 | 37 | 51 |
3X6+2X4 | 0.7/0.7 | 1.8 | 15.6 | 350 | 3.08/4.61 | 47 | 64 |
3X10+2X6 | 0.7/0.7 | 1.8 | 17.9 | 480 | 1.83/3.08 | 65 | 86 |
3X16+2X10 | 0.7/0.7 | 1.8 | 20.8 | 760 | 1.15/1.83 | 84 | 110 |
3X25+2X16 | 0.9/0.7 | 1.8 | 25.2 | 1040 | 0.727/1.15 | 110 | 140 |
3X35+2X16 | 0.9/0.7 | 1.8 | 26.8 | 1420 | 0.524/1.15 | 135 | 170 |
3X50+2X25 | 1.0/0.9 | 1.9 | 28.7 | 1830 | 0.387/0.727 | 170 | 205 |
3X70+2X35 | 1.1/0.9 | 2.0 | 32.2 | 2500 | 0.268/0.524 | 215 | 250 |
3X95+2X50 | 1.1/1.0 | 2.2 | 36.7 | 3400 | 0.193/0.387 | 265 | 300 |
3X120+2X70 | 1.2/1.1 | 2.3 | 40.8 | 4300 | 0.153/0.268 | 310 | 345 |
3X150+2X70 | 1.4/1.1 | 2.4 | 44.5 | 5200 | 0.124/0.268 | 350 | 385 |
3X185+2X95 | 1.6/1.1 | 2.6 | 50.5 | 6500 | 0.0991/0.193 | 405 | 435 |
3X240+2X120 | 1.7/1.2 | 2.8 | 56.1 | 8500 | 0.0754/0.153 | 480 | 500 |
3X300+2X150 | 1.8/1.4 | 3.0 | 63.7 | 10000 | 0.0601/0.124 | 555 | 565 |